IFM Pressure sensor with display PN2293 PN-025-REN14-MFRKG/US/ /V
Two switching outputs, one of them programmable as IO-Link and one as analog output
Red/green display for clear identification of the acceptable range
The process connection can be rotated for optimum alignment
With long-term stability thanks to high overload protection
Robust design for use in harsh industrial environments
Product characteristics | |
---|---|
Output signal | switching signal; analog signal; IO-Link; (configurable) |
Measuring range | -1...25 bar-14.5...362.5 psi-0.1...2.5 MPa |
Process connection | threaded connection 1/4" NPT Internal thread |
Application | |
System | gold-plated contacts |
Measuring element | ceramic-capacitive pressure measuring cell |
Application | for industrial applications |
Media | liquids and gases |
Medium temperature [°C] | -25...80 |
Min. bursting pressure | 350 bar5075 psi35 MPa |
Pressure rating | 150 bar2175 psi15 Mpa |
Vacuum resistance [mbar] | -1000 |
Type of pressure | relative pressure; vacuum |
MAWP (for applications according to CRN) | 70 bar1015 psi7 MPa |
Electrical data | |
Operating voltage [V] | 18...30 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] | < 35 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 0.3 |
Integrated watchdog | yes |
Inputs / outputs | |
Number of inputs and outputs | Number of digital outputs: 2; Number of analog outputs: 1 |
Outputs | |
Total number of outputs | 2 |
Output signal | switching signal; analog signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / closed; (configurable) |
Max. voltage drop switching output DC [V] | 2 |
Permanent current rating of switching output DC [mA] | 250 |
Switching frequency DC [Hz] | < 500 |
Number of analog outputs | 1 |
Analog current output [mA] | 4...20; (scalable 1:5) |
Max. load [Ω] | 500 |
Analog voltage output [V] | 0...10; (scalable 1:5) |
Min. load resistance [Ω] | 2000 |
Short-circuit protection | yes |
Type of short-circuit protection | yes (non-latching) |
Overload protection | yes |
Measuring/setting range | |
Measuring range | -1...25 bar-14.5...362.5 psi-0.1...2.5 MPa |
Analog start point | -1...20 bar-14.5...290 psi-0.1...2 MPa |
Analog end point | 4...25 bar58...362.5 psi0.4...2.5 MPa |
Factory setting / CMPT = 2 | |
Set point SP | -0.85...25 bar-12...362.5 psi-0.085...2.5 MPa |
Reset point rP | -0.95...24.9 bar-13.5...361 psi-0.095...2.49 MPa |
Min. difference between SP and rP | 0.15 bar1.5 psi0.015 MPa |
In steps of | 0.05 bar0.5 psi0.005 MPa |
Status_B High Resolution / CMPT = 3 | |
Set point SP | -0.84...25 bar-12.2...362.6 psi-0.084...2.5 MPa |
Reset point rP | -0.95...24.9 bar-13.7...361.1 psi-0.095...2.49 MPa |
Min. difference between SP and rP | 0.11 bar1.5 psi0.011 MPa |
In steps of | 0.01 bar0.1 psi0.001 MPa |
Accuracy / deviations | |
Notes on the accuracy / deviation | switch point accuracy, linearity error under DNV GL: < ± 1%: < ± 1% |
Switch point accuracy [% of the span] | < ± 0,4; (Turn down 1:1) |
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis deviation [% of the span] | < ± 0,1; (Turn down 1:1) |
Long-term stability [% of the span] | < ± 0,05; (Turn down 1:1; per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] | < ± 0,2; (-0...80 °C) |
Temperature coefficient span [% of the span / 10 K] | < ± 0,2; (-0...80 °C) |
Reaction times | |
Response time [ms] | < 1.5 |
Delay time programmable dS, dr [s] | 0...50 |
Damping for the switching output dAP [s] | 0...4 |
Damping for the analog output dAA [s] | 0...4 |
Max. response time analog output [ms] | 3 |
Software / programming | |
Parameter setting options | hysteresis / window; normally open / closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output |
Interfaces | |
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
SIO mode | yes |
Required master port class | A; (wenn PIN 2 nicht verbunden: B) |
Supported DeviceIDs | Type of operationDeviceIDFactory setting / CMPT = 2472Status_B High Resolution / CMPT = 3988 |
Note | For further information please see the IODD PDF file at "Downloads" |
Factory setting / CMPT = 2 | |
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
Min. process cycle time [ms] | 2.3 |
IO-Link resolution pressure [bar] | 0.01 |
IO-Link process data (cyclical) | Functionbit lengthpressure14binary switching information2 |
IO-Link functions (acyclical) | application specific tag |
Status_B High Resolution / CMPT = 3 | |
Profiles | Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000) |
Min. process cycle time [ms] | 3 |
IO-Link resolution pressure [bar] | 0.01 |
IO-Link process data (cyclical) | Functionbit lengthpressure16device status4binary switching information2 |
IO-Link functions (acyclical) | application specific tag |
Operating conditions | |
Ambient temperature [°C] | -25...80 |
Storage temperature [°C] | -40...100 |
Protection | IP 65; IP 67 |
Tests / approvals | |
EMC | DIN EN 61000-6-2DIN EN 61000-6-3 |
Shock resistance | DIN EN 60068-2-2750 g (11 ms) |
Vibration resistance | DIN EN 60068-2-620 g (10...2000 Hz) |
MTTF [years] | 138 |
UL approval | UL approval numberJ012 |
Pressure equipment directive | sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical data | |
Weight [g] | 223.5 |
Material | stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC |
Materials (wetted parts) | stainless steel (1.4404 / 316L); Al2O3 (ceramics); FKM |
Min. pressure cycles | 100 million |
Tightening torque [Nm] | > 50; (Depends on lubrication, seal and pressure rating) |
Process connection | threaded connection 1/4" NPT Internal thread |
Restrictor element integrated | no (can be retrofitted) |
Displays / operating elements | |
Display | Display unit3 x LED, green (bar, psi, MPa)Switching status2 x LED, yellowMeasured valuesalphanumeric display, red/green 4-digit |
Remarks | |
Pack quantity | 1 pcs. |
Electrical connection | |
Connection | Connector: 1 x M12; Contacts: gold-plated |
Related Products
PN2293
PN7294
PN2694
PN7094
PN7092
PN2298
PN7292
PN7694
PN2271
PN7271
PN2299
PN2693
PN7270
PN7014
PN7015
PN7012
PN2094
PN2698
PN7071
PN7293
PN2292
PN2270
PN2671
Windy Wang
HONGKONG XIEYUAN TECH CO., LIMITED
Add: 7-A16,Caishen Commercial Plaza,Hankou Railway Station,Wuhan,China
Tel: +86-27-8588 3233 | Fax:+86-27-8530 9780 | Mobile/Whatsapp :+86 15972199006 | Skype: windy@hkxytech.com
Mail: windy@hkxytech.com
Website: http://www.hkxytech.com/ | GMT/UTC +8