Pressure sensor
IFM Optical level sensor O1D300 O1DLF3KG/IO-LINK

IFM Optical level sensor O1D300 O1DLF3KG/IO-LINK

Model: O1D300

$1.00

Supplier: IFM

Categories: Pressure sensor

After sales service. If you have any questions, click here.

Product Description

IFM Optical level sensor O1D300 O1DLF3KG/IO-LINK


IFM O1D300 Product Picture

  • Reliable optical level measurement with high ranges up to 9.8 m

  • Scalable measuring range and window function

  • Two switching outputs, one of them programmable as analog output

  • Wide range of components for quick mounting and precise fine adjustment

  • Excellent price/performance ratio

Product characteristics
Measuring range [m]0.2...10; (white paper 200 x 200 mm 90 % remission)
Communication interfaceIO-Link
Laser protection class2
Housingrectangular
Dimensions [mm]59 x 42 x 52
Electrical data
Operating voltage [V]18...30 DC; (cULus - Class 2 source required)
Current consumption [mA]< 150
Protection classIII
Reverse polarity protectionyes
Typ. lifetime [h]50000
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 2; Number of analog outputs: 1
Outputs
Total number of outputs2
Electrical designPNP
Number of digital outputs2
Output functionnormally open / closed; (programmable)
Max. current load per output [mA]200
Number of analog outputs1
Analog current output [mA]4...20; (IEC 61131-2)
Max. load [Ω]250
Analog voltage output [V]0...10; (IEC 61131-2)
Min. load resistance [Ω]5000
Short-circuit protectionyes
Type of short-circuit protectionyes (non-latching)
Overload protectionyes
Monitoring range
Max. light spot width [mm]15
Max. light spot height [mm]15
Light spot dimensions refer to10 m
Background suppression [m]10...100
Measuring/setting range
Measuring range [m]0.2...10; (white paper 200 x 200 mm 90 % remission)
Sampling rate [Hz]1...33
Interfaces
Communication interfaceIO-Link
Transmission typeCOM2 (38,4 kBaud)
IO-Link revision1.1
SDCI standardIEC 61131-9
ProfilesSmart Sensor: Sensor Identification; Binary Data Channel; Process Value; Sensor Diagnosis
SIO modeyes
Required master port classA
Process data analog2
Process data binary2
Min. process cycle time [ms]6
Supported DeviceIDsType of operationDeviceIDdefault813
Operating conditions
Ambient temperature [°C]-10...60
ProtectionIP 67
Tests / approvals
EMCEN 60947-5-2
Laser protection class2
Notes on laser protectionCaution:Laser lightPower:<= 4,0 mWWave length:650 nmpulse:1,3 nsDo not stare into beam.Avoid exposure to the laser light.laser class:2EN / IEC60825-1:2007EN / IEC60825-1:2014Complies with 21 CFR 1040 except for deviations pursuant to Laser Notice No. 50, dated June 2007.
MTTF [years]107
Mechanical data
Weight [g]325.5
Housingrectangular
Dimensions [mm]59 x 42 x 52
Materialhousing: diecast zinc; front lens: glass; LED window: PC
Lens alignmentSide sensing
Displays / operating elements
DisplaySwitching status2 x LED, yellowPowerLED, greenDistance, programmingalphanumeric display, 4-digit
Accessories
Accessories (optional)Protective cover, E21133
Remarks
RemarkscULus - Class 2 source required
Pack quantity1 pcs.
Electrical connection
ConnectionConnector: 1 x M12
Other data
ParameterSetting rangeFactory settingUnicm, m, inchcmOU1Hno, Hnc, Fno, FncHnoSP1 [cm]20.0...999.5100.0rP1 [cm]20.0...999.580.0OU2Hno, Hnc, Fno, Fnc, I, UISP2 [cm]20.0...999.5200.0rP2 [cm]20.0...999.5180.0ASP [cm]20.0...999.50AEP [cm]20.0...999.5979.5dr1 [s]0...0.1...50dr2 [s]0...0.1...50FOU1ON ; OFFOFFFOU2ON ; OFFOFFdFO [s]0...0.1...50EMP [cm]20.0...999.520.0cMEd [cm]20.0...999.5-dISON ; OFFONmEAn [s]OFF ; 1...60OFFrATE [Hz]1...3315
Repeatability / Accuracy
Repeatability of the measured valuesAccuracywhite (90 % remission)grey (18 % remission)white (90 % remission)grey (18 % remission)20.0...100.0 cm± 0.45 cm± 0.6 cm± 1.5 cm± 1.6 cm100.0...200.0 cm± 0.5 cm± 0.8 cm± 1.5 cm± 1.8 cm200.0...400.0 cm± 1.6 cm± 1.9 cm± 2.5 cm± 3.0 cm400.0...600.0 cm± 2.4 cm± 3.3 cm± 3.5 cm± 4.5 cm600.0...1000.0 cm± 5.0 cm± 6.5 cm
Sampling rate15HzExtraneous light on the object< 40 klx
Repeatability / Accuracy
Repeatability of the measured valuesAccuracywhite (90 % remission)grey (18 % remission)white (90 % remission)grey (18 % remission)20.0...200.0 cm± 1.4 cm± 1.4 cm± 2.4 cm± 2.4 cm200.0...400.0 cm± 2.5 cm± 3.0 cm± 3.5 cm± 4.0 cm400.0...600.0 cm± 3.1 cm± 4.5 cm± 4.1 cm± 5.5 cm600.0...1000.0 cm± 6.0 cm± 7.0 cm
Sampling rate15HzExtraneous light on the object40...100 klx
Repeatability / Accuracy
Repeatability of the measured valuesAccuracywhite (90 % remission)grey (18 % remission)white (90 % remission)grey (18 % remission)20.0...100.0 cm± 0.4 cm± 0.45 cm± 1.4 cm± 1.5 cm100.0...200.0 cm± 0.45 cm± 0.6 cm± 1.5 cm± 1.6 cm200.0...400.0 cm± 1.35 cm± 1.4 cm± 2.3 cm± 2.4 cm400.0...600.0 cm± 1.9 cm± 2.1 cm± 2.9 cm± 3.1 cm600.0...1000.0 cm± 3.7 cm± 4.7 cm
Sampling rate1 HzExtraneous light on the object< 40 klx
Repeatability / Accuracy
Repeatability of the measured valuesAccuracywhite (90 % remission)grey (18 % remission)white (90 % remission)grey (18 % remission)20.0...200.0 cm± 1.0 cm± 1.0 cm± 2.0 cm± 2.0 cm200.0...400.0 cm± 1.8 cm± 1.9 cm± 2.8 cm± 2.9 cm400.0...600.0 cm± 2.3 cm± 2.7 cm± 3.3 cm± 3.7 cm600.0...1000.0 cm± 3.8 cm± 4.8 cm
Sampling rate1 HzExtraneous light on the object40...100 klxRange on black object (6 % remission)<= 4000 mmThe values apply atconstant ambient conditions23 °C / 960 hPaminimum power-on time in minutes10

Related Products


O1D100Photoelectric distance sensor

O1D300Optical level sensor

O1D155Photoelectric distance sensor

O1D102Photoelectric distance sensor

O1D105Photoelectric distance sensor

O1D106Photoelectric distance sensor

O1D101Photoelectric distance sensor

O1D103Photoelectric distance sensor

O1D108Photoelectric distance sensor

O1D104Photoelectric distance sensor


Windy Wang
HONGKONG XIEYUAN TECH CO., LIMITED
Add: 7-A16,Caishen Commercial Plaza,Hankou Railway Station,Wuhan,China
Tel: +86-27-8588 3233 | Fax:+86-27-8530 9780 | Mobile/Whatsapp :+86 15972199006 | Skype: windy@hkxytech.com
Mail: windy@hkxytech.com
Website: http://www.hkxytech.com/ | GMT/UTC +8


Related Products