Feature of O1D100


  • Reliable optical distance measurement with high ranges up to 10 m

  • Two switching outputs, one of them programmable as analogue output

  • Scalable measuring range and window function

  • Use in applications with background suppression

  • Excellent price/performance ratio

Product characteristics of O1D100
Laser protection class2
Housingrectangular
Electrical data of O1D100
Operating voltage [V]18...30 DC; (operating voltage "supply class 2" according to cULus)
Current consumption [mA]< 150
Protection classIII
Reverse polarity protectionyes
Typ. lifetime [h]50000
Inputs / outputs of O1D100
Number of inputs and outputsNumber of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs2
Electrical designPNP
Number of digital outputs2
Output functionnormally open / normally closed; (parameterisable)
Max. current load per output [mA]200
Number of analogue outputs1
Analogue current output [mA]4...20; (IEC 61131-2)
Max. load [Ω]250
Analogue voltage output [V]0...10; (IEC 61131-2)
Min. load resistance [Ω]5000
Short-circuit protectionyes
Type of short-circuit protectionpulsed
Overload protectionyes
Detection zone
Max. light spot width [mm]15
Max. light spot height [mm]15
Light spot dimensions refer to10 m
Background suppression [m]0...19
Measuring/setting range
Measuring range [m]0.2...10; (white paper 200 x 200 mm 90% remission)
Sampling rate [Hz]1...50
Interfaces
Communication interfaceIO-Link
Transmission typeCOM2 (38,4 kBaud)
IO-Link revision1.1
SDCI standardIEC 61131-9
ProfilesSmart Sensor: Sensor Identification; Binary Data Channel; Process Value; Sensor Diagnosis
SIO modeyes
Required master port typeA
Process data analogue2
Process data binary3
Min. process cycle time [ms]6
Supported DeviceIDsType of operationDeviceIDDefault806
Operating conditions
Ambient temperature [°C]-10...60
ProtectionIP 67
Tests / approvals
EMCEN 60947-5-2
Laser protection class2
Notes on laser protectionCaution:laser lightPower:<= 4 mWWave length:650 nmpulse:1,3 nsDo not stare into beam.Avoid exposure to the laser light.laser class:2EN / IEC60825-1:2007EN / IEC60825-1:2014Complies with 21 CFR 1040 except for deviations pursuant to Laser Notice No. 50, dated June 2007.
MTTF [years]182
Mechanical data
Weight [g]303
Housingrectangular
Dimensions [mm]59 x 42 x 52
Materialshousing: diecast zinc; front lens: glass; LED window: PC
Lens alignmentside lens
Displays / operating elements
Displayswitching status2 x LED, yellowoperationLED, greendistance value, programmingalphanumeric display, 4-digit
Accessories
Accessories (optional)Protective cover, E21133
Remarks
RemarksFor more information about the measuring range / application please refer to the operating instructions.
Pack quantity1 pcs.
Electrical connection
ConnectionConnector: 1 x M12
Other data
ParameterSetting rangeFactory settingUnimm, m, inchmmOU1Hno, Hnc, Fno, FncHnoSP1 [mm]200...99991000nSP1 [mm]200...9999800FSP1 [mm]200...99991200OU2Hno, Hnc, Fno, Fnc, I, UISP2 [mm]200...99992000nSP2 [mm]200...99991800FSP2 [mm]200...99992200ASP [mm]0...99990AEP [mm]0...99999999rATE [Hz]1...5050dS1 [s]0...0.1...50dr1 [s]0...0.1...50dS2 [s]0...0.1...50dr2 [s]0...0.1...50dFo [s]0...0.1...50dISd1...3 ; rd1...3; OFFd3
repeatability/accuracy
read/write distance (mm)repeatability of the measured valuesAccuracywhite (90 % remission)grey (18 % remission)white (90 % remission)grey (18 % remission)200...1000 mm± 5.0 mm±7.5 mm± 15.0 mm± 18.0 mm1000...2000 mm± 5.5 mm±10.0 mm± 15.0 mm± 20.0 mm2000...4000 mm± 17.5 mm±22.5 mm± 25.0 mm± 32.0 mm4000...6000 mm± 27.5 mm±40.0 mm± 35.0 mm± 50.0 mm6000...10000 mm± 60.0 mm± 70.0mm
Sampling rate50 HzExtraneous light on the object< 40 klx
repeatability/accuracy
read/write distance (mm)repeatability of the measured valuesAccuracywhite (90 % remission)grey (18 % remission)white (90 % remission)grey (18 % remission)200...1000 mm± 16.5 mm±16.5 mm± 26.5 mm± 26.5 mm1000...2000 mm± 16.5 mm±16.5 mm± 26.5 mm± 26.5 mm2000...4000 mm± 30.0 mm±37.0 mm± 40.0 mm± 47.0 mm4000...6000 mm± 37.0 mm±57.0 mm± 47.0 mm± 67.0 mm6000...10000 mm± 75.0 mm—± 85.0mm—
Sampling rate50 HzExtraneous light on the object40...100 klx
repeatability/accuracy
read/write distance (mm)repeatability of the measured valuesAccuracywhite (90 % remission)grey (18 % remission)white (90 % remission)grey (18 % remission)200...1000 mm± 4.0 mm±4.5 mm± 14.0 mm± 15.0 mm1000...2000 mm± 4.5 mm±6.0 mm± 14.5 mm± 16.0 mm2000...4000 mm± 13.5 mm±14.5 mm± 23.5 mm± 24.0 mm4000...6000 mm± 19.0 mm±21.0 mm± 29.0 mm± 31.0 mm6000...10000 mm± 37.0 mm–± 47.0mm–
Sampling rate1 HzExtraneous light on the object< 40 klx
repeatability/accuracy
read/write distance (mm)repeatability of the measured valuesAccuracywhite (90 % remission)grey (18 % remission)white (90 % remission)grey (18 % remission)200...1000 mm± 10.0 mm± 10.0 mm± 20.0 mm± 20.0 mm1000...2000 mm± 10.0 mm± 10.0 mm± 20.0 mm± 20.0 mm2000...4000 mm± 17.0 mm± 18.0 mm± 27.0 mm± 28.0 mm4000...6000 mm± 22.0 mm± 25.0 mm± 32.0 mm± 35.0 mm6000...10000 mm± 37.0 mm–± 47.0mm–
Sampling rate1 HzExtraneous light on the object< 40...100 klx--Range on black object (6 % remission)<= 4000 mm--The values apply atconstant ambient conditions23 °C / 960 hPaminimum power-on time in minutes10

IFM O1D100 Photoelectric distance sensor

PDE AND BRE


if you are intersted in more Allen-Bradley product, Please feel free to contct below contact me :windy@hkxytech.com 


Windy Wang 
HONGKONG XIEYUAN TECH CO., LIMITED  
Add: 7-A16,Caishen Commercial Plaza,Hankou Railway Station,Wuhan,China
Tel: +86-27-8588 3233 | Fax:+86-27-8530 9780 | Mobile/Whatsapp :+86 15972199006 | Skype: windy@hkxytech.com
Mail: windy@hkxytech.com 
Website:  http://www.hkxytech.com/   | GMT/UTC +8

Related Products