100% Original MTL3072 TEMPERATURE CONVERTER 3-wire RTD input In Good Price Ready To Ship

100% Original MTL3072 TEMPERATURE CONVERTER 3-wire RTD input In Good Price Ready To Ship

Model: MTL3072

$1.00

Supplier: Products

Categories: MTL

After sales service. If you have any questions, click here.

Product Description

100% Original MTL3072 TEMPERATURE CONVERTER 3-wire RTD input In Good Price Ready To Ship


MTL3072 TEMPERATURE CONVERTER 3-wire RTD input.The MTL3072 accepts a signal from a 3-wire resistance temperature detector (RTD) in the hazardous area, and converts it to a 4/20mA loop current 


The MTL3072 accepts a signal from a 3-wire resistance temperature detector (RTD) in the hazardous area, and converts it to a 4/20mA loop current in the safe area proportional to resistance (but not temperature). Calibration is carried out by the user via controls located in the top and the side of the unit. Input zero and span are selected by switches (coarse adjustment) and potentiometers (fine adjustment).


SPECIFICATION OF MTL3072 

See also 'Common specification'

Number of channels

One, fully floating

Signal source

3-wire platinum RTD to BS1904/DIN 43760 (100Ω at 0°C)

–terminals 5, 6 & 7

Location of signal source

Zone 0, IIC, T4 hazardous area if suitably certified

Div 1, Group A, hazardous location

Span (fully adjustable by switches and potentiometers)

25 to 800°C

Zero (fully adjustable by switches and potentiometers)

–200 to +400°C

Common-mode ac rejection

<0.1% error for 250V rms, 50Hz

Series-mode ac rejection

<0.1% error for 50Hz rms input equal to 2mV or (span in

Ω/30)mV, whichever is the greater

Loop supply voltage

15 to 35V dc

Output range

4 to 20mA

Maximum load resistance

50(Vs –15) Ω

Response time

Settles to within 10% of final value after typically 250ms

Calibration accuracy at 20°C

(including non-linearity, hysteresis and repeatability)

Within 0.1% of span

Temperature drift (maximum)

Zero: the greater of the following:–

±0.01% of span/°C or 10mΩ/°C

Span: ±0.005% of input span/°C

Suppression/elevation (E): ±0.01% of E/°C

RTD excitation current

400µA

Line resistance

100Ω maximum in each line

Power dissipation within unit

0.46W maximum at 35V with 20mA signal

Replaceable fuse

50mA, 5 x 20mm glass to DIN 41571 sheet 2, semi-time-lag (M)

Safety description

13.6V, 142Ω, 95.3mA, Ceq = 56.5nF, Leq = 2.2mH,

Um = 250V rms or dc

FM max entity parameters

Voc = 13.6V, Isc = 95.3mA, Ca = 1.15µF, La = 1.8mH

Weight

170g



100% Original MTL3072 TEMPERATURE CONVERTER 3-wire RTD input In Good Price Ready To Ship

MTL3992

MTL3099

MTL3081

MTL3073

MTL3072

MTL3071

MTL3058

MTL3059

MTL3054

MTL3052

MTL3046B

MTL3045

MTL3043

MTL3042

MTL3041

MTL3021

MTL3014

MTL3013

MTL3011


PDE AND BRE


if you are intersted in more Allen-Bradley product, Please feel free to contct below contact me :windy@hkxytech.com 


Windy Wang 
HONGKONG XIEYUAN TECH CO., LIMITED  
Add: 7-A16,Caishen Commercial Plaza,Hankou Railway Station,Wuhan,China
Tel: +86-27-8588 3233 | Fax:+86-27-8530 9780 | Mobile/Whatsapp :+86 15972199006 | Skype: windy@hkxytech.com
Mail: windy@hkxytech.com 
Website:  http://www.hkxytech.com/   | GMT/UTC +8




Related Products