100% Original MTL3071 TEMPERATURE CONVERTER THC or emf input In Good Price Ready To Ship
MTL3071 TEMPERATURE CONVERTER THC or emf input.The MTL3071 accepts a low-level dc signal from a temperature sensor in a hazardous area, and converts it into a 4/20mA loop current in the safe area.
The MTL3071 accepts a low-level dc signal from a temperature sensor in a hazardous area, and converts it into a 4/20mA loop current in the safe area proportional to millivolts (but not temperature). It can monitor any one of six types of thermocouple, or a millivolt signal from an emf source. Calibration is carried out by the user via controls located in the top and the side of the unit. This can be effected without the use of a thermocouple since the unit's built-in cold junction compensation (CJC) is zeroed at 0°C, and can be bypassed. Thermocouple type is switch-selectable, as is the optional safety drive which initiates either a high or low output in the event of thermocouple burnout or any cable breakage. Input zero and span are selected by switches (coarse adjustment) and potentiometers (fine adjustment).
SPECIFICATION OF MTL3071
See also 'Common specification'
Number of channels
One, fully floating
Signal source (selected by switches)
Type E, J, K, N, R or T thermocouple to BS 4937 –
terminals 5 & 6
EMF input – terminals 5 & 7
Location of signal source
Zone 0, IIC, T4 hazardous area if suitably certified
Div 1, Group A, hazardous location
Span (fully adjustable by switches and potentiometers)
4 to 60mV
Zero (fully adjustable by switches and potentiometers)
–12 to +60mV
Common-mode ac rejection
<0.1% error for 250V rms, 50Hz
Series-mode ac rejection
<0.1% error for 50Hz rms input equal to half of span
Loop supply voltage
15 to 35V dc
Output range
4 to 20mA
Maximum load resistance
50(Vs –15) Ω
Response time
Settles to within 10% of final value after typically 350ms
Calibration accuracy at 20°C
(including non-linearity, hysteresis and repeatability)
Within 0.1% of span (emf input)
Within 0.1% of span ± 1°C (THC input)
Temperature drift (maximum)
Zero: the greater of the following:–
±0.01% of span/°C or ±1µV/°C (emf input)
as above, ±0.03°C/°C (THC input except type R)
as above, ±0.07°C/°C (THC type R input)
Span: ±0.005% of input span/°C
Suppression/elevation (E): ±0.01% of E/°C
Cold junction compensation (CJC)
Referenced to 0°C
Safety drive on THC burnout (selected by switches)
Upscale or downscale, or off
Input current
<1nA (safety drive off)
<75nA (safety drive on)
Power dissipation within unit
0.46W maximum at 35V with 20mA signal
Replaceable fuse
50mA, 5 x 20mm glass to DIN 41571 sheet 2, semi-time-lag (M)
Safety description
11V, 3.79kΩ, 2.9mA, Ceq = 0, Leq = 2.2mH,
Um = 250V rms or dc
FM max entity parameters
Voc = 11.0V, Isc = 2.9mA, Ca = 1.9µF, La = 1000mH
Weight
170g
MTL3992
MTL3099
MTL3081
MTL3073
MTL3072
MTL3071
MTL3058
MTL3059
MTL3054
MTL3052
MTL3046B
MTL3045
MTL3043
MTL3042
MTL3041
MTL3021
MTL3014
MTL3013
MTL3011
Windy Wang
HONGKONG XIEYUAN TECH CO., LIMITED
Add: 7-A16,Caishen Commercial Plaza,Hankou Railway Station,Wuhan,China
Tel: +86-27-8588 3233 | Fax:+86-27-8530 9780 | Mobile/Whatsapp :+86 15972199006 | Skype: windy@hkxytech.com
Mail: windy@hkxytech.com
Website: http://www.hkxytech.com/ | GMT/UTC +8