100% Original and Brand New MTL2000 range MTL2215 Switch operated relay ~ IS output product has been discontinued.
The MTL2215 enables either one or two separate IS circuits in a hazardous area to be relay-contact controlled by a single on/off switch or logic signal in a safe area. Applications include the calibration of strain-gauge bridges, changing the tone of an IS sounder, the testing of IS fire alarms, and the transfer of safe-area signals into an annunciator with IS input terminals not segregated from each other. The output-relay contacts are certified as ‘non-energystoring’ apparatus, and can be connected to any IS circuit without further certification, provided that separate IS circuits are such that they would still remain safe if connected together.
SPECIFICATION OF MTL2215
See also ‘Common specification’
Number of channels
One, fully floating
Location of control circuit
Safe area
Input/output characteristics
Relay energised if <27kΩ or <1V applied
Relay de-energised if >54kΩ or >2V applied (50V maximum)
Hysteresis, nominal: 16kΩ or 0.6V
Power supply failure protection
Relay de-energised if supply fails
Response time
50ms, nominal
Contacts (suitable for connection to IS circuits)
2-pole changeover
Contact rating (non-IS applications)
250V,5A,500VA (ac), resistive loads, reactive loads must be
suppressed
250V,5A,250W (dc), resistive loads, reactive loads must be
suppressed
Contact life expectancy (non-IS applications)
2 x 105 operations at maximum load
LED indicator
ON when relay energised
Consumption
0.9 to 1.4W (ac versions)
60mA (24V dc version)
Ambient temperature limits
–20 to +55°C (all versions, close packed)
–20 to +60°C (all versions, at least 5mm apart)
–40 to +80°C (all versions, storage)
Safety description (each channel)
Non-energy-storing apparatus: relay contacts may be
connected to any certified IS circuit in Zone 0 without further
certification
Note: The 2-pole changeover contacts may be used to switch separate IS
circuits only if these remain intrinsically safe when interconnected, since the
two sets of relay contacts are not segregated from each other
MTL2220
MTL2215
MTL2213
MTL2211
MTL2210B
MTL2442B
MTL2441B
MTL2316
MTL2315
MTL2314
MTL2313
MTL2242
MTL2241
MTL2220
MTL2215
MTL2213
MTL2211
MTL2210B
Windy Wang
HONGKONG XIEYUAN TECH CO., LIMITED
Add: 7-A16,Caishen Commercial Plaza,Hankou Railway Station,Wuhan,China
Tel: +86-27-8588 3233 | Fax:+86-27-8530 9780 | Mobile/Whatsapp :+86 15972199006 | Skype: windy@hkxytech.com
Mail: windy@hkxytech.com
Website: http://www.hkxytech.com/ | GMT/UTC +8