100% Original New MTL2000 range MTL2213 3 channel Switch/proximity detector relay has been discontinued now In Ready Stock
The MTL2213 enables three 100VA safe-area loads to be controlled independently by three light-duty on/off switches or certified proximity detectors in a hazardous area. Switches and proximity detectors may be mixed. The three input circuits are interconnected but fully floating. For proximity-detector and some switch applications, a phase-reverse link allows alarm conditions to be signalled for either state of the sensors. ‘Alarm’ means relays de-energised with their on/off contacts open, and all three circuits have to operate in the same fashion. This compact low-cost unit is suitable for a wide variety of applications. The MTL2213 supersedes the MTL2212 for which it is a direct replacement, except that only terminal 8 can be used for connecting to earth.
SPECIFICATION OF MTL2213
See also ‘Common specification’
Number of channels
Three, interconnected, fully floating
Location of switches
Zone 0, IIC, T6 hazardous area
Div 1, Group A, hazardous location
Location of proximity detectors
Zone 0, IIC, T4–T6 if suitably certified
Div 1, Group A, hazardous location
Voltage applied to each sensor
7.7 to 9.0V dc from 1kΩ
Input/output characteristics (each channel)
Relay energised if >2.1mA* (<2kΩ) in sensor circuit
Relay de-energised if <1.2mA* (>10kΩ) in sensor circuit
Hysteresis: 200μA (650Ω ) nominal
*NAMUR and DIN 19234 standards for proximity detectors
Phase reverse facility
Operation of all 3 relays reversed by linking terminals 7 & 8
Power supply failure protection
All three relays de-energised, contacts open, if supply fails
Broken line protection (each channel, normal phase only)
Relay de-energised, contacts open, if either line broken
Fail-safe earth fault protection (each channel, normal
phase only)
(Enabled by connecting terminal 8 to earth)
Relay de-energised if <25Ω to earth, total for both lines
Relay not de-energised if >52kΩto earth, total for both lines
‘No-fail’ earth fault protection (either phase)
(Enabled by connecting terminal 8 to MTL4220)
Fault on any line proclaimed: unit continues working
Response time (each channel)
50ms, nominal
Contacts (each channel)
On/off, open when relay de-energised
Contact rating
250V,5A,100VA (ac), resistive loads, reactive loads must be
suppressed
250V,5A,100W (dc), resistive loads, reactive loads must be
suppressed
MTL2220
MTL2215
MTL2213
MTL2211
MTL2210B
MTL2442B
MTL2441B
MTL2316
MTL2315
MTL2314
MTL2313
MTL2242
MTL2241
MTL2220
MTL2215
MTL2213
MTL2211
MTL2210B
Windy Wang
HONGKONG XIEYUAN TECH CO., LIMITED
Add: 7-A16,Caishen Commercial Plaza,Hankou Railway Station,Wuhan,China
Tel: +86-27-8588 3233 | Fax:+86-27-8530 9780 | Mobile/Whatsapp :+86 15972199006 | Skype: windy@hkxytech.com
Mail: windy@hkxytech.com
Website: http://www.hkxytech.com/ | GMT/UTC +8