Pepperl+Fuchs HiCTB08-SCT-44C-SC-RA Termination Board Has Best Price In Stock
The termination board has 8 plug-in slots for isolators. Any isolator can be inserted into any slot, enabling a mixture of I/O types on one termination board.
The termination board features fixed screw terminals for the field side connection and for the control side connection along with a HART cordset for interconnection to a separate HART Communication Board. Information about missing supply voltage of the isolators is available for the system as volt-free contact at the redundant power supply terminals. Wiring errors from field side will be reported via the same relay contact, if this function supported by the the isolators.
The termination board is supplied with a robust plastic housing as standard. This design permits the fast and reliable installation on 35 mm DIN mounting rail acc. to EN 60715 in the cabinet.
Datasheet excerpt: Technical data of HiCTB08-SCT-44C-SC-RA
Supply | ||
---|---|---|
Connection | X20: terminals 3, 5(+); 4, 6(-) | |
Nominal voltage | 24 V DC , in consideration of rated voltage of used isolators | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | ≤ 10 % | |
Fusing | 2 A , in each case for 8 modules | |
Power dissipation | ≤ 500 mW , without modules | |
Reverse polarity protection | yes | |
Redundancy | ||
Supply | Redundancy available. The supply for the isolators is decoupled, monitored and fused. | |
Fault indication output | ||
Connection | X20: terminals 1, 2 | |
Output type | volt-free contact | |
Switch behaviour | no fault: relay contact closed power supply fault: relay contact open module fault: relay contact open | |
Contact loading | 30 V DC, 1 A | |
Indicators/settings | ||
Display elements | LED PWR1 (termination board power supply), green LED LED PWR2 (termination board power supply), green LED LED FAULT (fault indication), red LED - LED lits: module fault - LED flashes: power supply fault | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | ||
Field side | explosion hazardous area: 4 screw terminals per module , blue | |
Control side | non-explosion hazardous area: 4 screw terminals per module , black | |
Supply | pluggable screw terminals , black | |
Fault output | pluggable screw terminals , black | |
Core cross section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 12 AWG) | |
Material | housing: polycarbonate, 10 % glass fiber reinforced | |
Mass | approx. 450 g | |
Dimensions | 108 x 200 x 163 mm (4.25 x 7.9 x 6.42 inch) (W x H x D) , depth including module assembly | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
FC-GPCS-RIO16-PF |
Termination Board |
System board for Honeywell Universal Safety IO, System board for Honeywell Universal Process IO, For 16-channel cards USIO and UPIO, For 16 modules, Recommended modules: HiC2831R2 (DI), HiC2853R2 (DI), HiC2871 (DO), HiC2025 (AI), HiC2031 (AO), Recommended system cable: CAB-HON-**-S37C32-MX-01000, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Universal, Manufacturer: Honeywell |
HiATB01-HART-2X16 |
HART Communication Board |
2 x 16-channel, 24 V DC supply, Suitable for HART communication, Dual RS 485 connections, Used with HiD/HiC Termination Boards, LED indicator for supply status, Splitting: 2 x 16 |
HiATB01-HART-4X8-Y1 |
HART Communication Board |
4 x 8-channel, 24 V DC supply, Suitable for HART communication, Dual RS 485 connections, Used with HiD/HiC Termination Boards, LED indicator for supply status, Splitting: 4 x 8 |
HiCTB08-FBM-RAC-SC-IO08 |
Termination Board |
System board for Schneider, Foxboro FBM series, For 8 modules, For 8-channel cards FBM201/214(b)/216(b) (AI), FBM215/218/237 (AO), FBM204/205 (AO/AI), FBM244 (AI/AO), FBM247/248 (UIO), 24 V DC supply, Recommended modules: HiC2025(A) (AI), HiC2025ES (AI), HiC2031 (AO), HiC2081 (TI), HiC2831R5 (DI), HiC2883 (DO), HiC2441 (UIO), Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 25-pin, Number of modules: 8, Signal type: Universal, Manufacturer: Foxboro |
HiCTB08-SCT-44C-SC-RA |
Termination Board |
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: screw terminals, black, Number of modules: 8, Number of channels per module: 1 , 2, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiCTB16-SCT-44C-SC-RA |
Termination Board |
For 16 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: screw terminals, black, Number of modules: 16, Number of channels per module: 1 , 2, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiDTB08-SCT-99C-SC-RA |
Termination Board |
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO, Hazardous area: screw terminals, blue, Non-hazardous area: screw terminals, black, Number of modules: 8, Number of channels per module: 2 , 4, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiSHPSM/32/MM-01 |
HART Termination Board |
32-channel, 24 V DC supply, Interface for serial or parallel wiring options, Dual RS 485 connections, Slot for HART Multiplexer, Number of channels: 32 unbalanced signal loops |
HiCTB16-FBM-RAC-SC-AI16 |
Termination Board |
System board for Schneider, Foxboro FBM series, For 16 modules, For 16-channel AI card FBM211, 24 V DC supply, Recommended modules: HiC2025(A) (AI), HiC2025ES (AI), HiC2081 (TI), Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Foxboro, Control system type: FBM |
HiCTB16-FBM-RAC-SC-DI16 |
Termination Board |
System board for Schneider, Foxboro FBM series, For 16 modules, For 16-channel DI card FBM207b, 24 V DC supply, Recommended modules: HiC2821 (DI), HiC2841 (DI), Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Foxboro, Control system type: FBM |
HiCTB16-FBM-RAC-SC-DI32 |
Termination Board |
System board for Schneider, Foxboro FBM series, For 16 modules, For 32-channel DI card FBM217, 24 V DC supply, Recommended modules: HiC2822 (DI), HiC2842 (DI), Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Foxboro, Control system type: FBM |
HiCTB16-FBM-RAC-SC-DO16 |
Termination Board |
System board for Schneider, Foxboro FBM series, For 16 modules, For 16-channel DO card FBM242c, 24 V DC supply, Recommended modules: HiC2871A (DO), HiC2883 (DO), Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Foxboro, Control system type: FBM |
HiCTB16-SDC-24C-SC-RA |
Termination Board |
For 16 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiCTB16-TRX-RAC-PL-AI16 |
Termination Board |
System board for Schneider Electric, Tricon CX series by Triconex, TAN48 approval, For 32-channel (16+16) AI cards 3722X and 3723X, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2025ES (AI), HiC2081 (TI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon CX |
HiCTB16-TRX-RAC-PL-DI16 |
Termination Board |
System board for Schneider Electric, Tricon CX series by Triconex, TAN48 approval, For 32-channel (16+16) DI card 3506X, For 16 modules, Recommended modules: HiC2821 (DI), HiC2841 (DI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon CX |
HiCTB16-TRX-RAC-PL-DI32 |
Termination Board |
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel DI card 3506X, For 16 modules, 24 V DC supply, Recommended modules: HiC2822 (DI), HiC2842 (DI), Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon CX |
HiCTB16-TRX-RAC-PL-DO16 |
Termination Board |
System board for Schneider Electric, Tricon CX series by Triconex, TAN48 approval, For 32-channel (16+16) DO card 3626X, For 16 modules, Recommended modules: HiC2871A (DO), HiC2873 (DO), HiC2883 (DO), HiC5861 (DO), HiC5863 (DO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Triconex, Control system type: Tricon CX |
HiCTB16-TRX-RAC-PL-IO16 |
Termination Board |
System board for Schneider Electric, Tricon CX series by Triconex, TAN48 approval, For 16-channel universal I/O card 3902(A)X and AO card 3809(A)X, For 16 modules, Supported signal types: DI/DO/AI/TI/AO/UIO, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: Sub-D connector (male), 50-pin, Up to SIL 3 acc. to IEC/EN 61508, Number of modules: 16, Signal type: Analog output |
Universal, Manufacturer: Triconex, Control system type: Tricon CX |
SC-GPCS-UNI16-PF |
Termination Board |
System board for Honeywell Experion PKS, Series C, For 16-/32-channel cards CC-TDIL01/11, CC-TDOB01/11, CC-TAIX01/11 and CC-TAOX01/11, For 16 modules, Recommended modules: HiC2821 (DI), HiC2871 (DO), HiC2025 (AI), HiC2031 (AO), Recommended system cable: CAB-HON-**-S37C32-MX-01000, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Universal, Manufacturer: Honeywell |
HiCTB08-SDC-44C-SC-RA |
Termination Board |
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 8, Number of channels per module: 1 , 2, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiCTB16-YC3-RRB-AK-CC-DX32 |
Termination Board |
System board for Yokogawa CENTUM VP, For 32-channel DI card ADV151, For 16 modules, Recommended modules: HiC2822 (DI), HiC2842 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiCTB16-YRS-RRB-KS-CC-AI16 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 16-channel AI card SAI143, For 16 modules, Recommended modules: HiC2025(A) (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiDTB08-SPT-99C-SP-RS-Y1 |
Termination Board |
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO, Hazardous area: spring terminals, blue, Non-hazardous area: spring terminals, black, Number of modules: 8, Number of channels per module: 2 , 4, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
FC-GPCD-SDI16-PF |
Termination Board |
System board for Honeywell Safety Manager, For 16-channel DI card SDI-1624, For 8 modules, Recommended module: HiC2822 (DI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: SiC plug, 20-pin, Number of modules: 8, Signal type: Digital Input, Manufacturer: Honeywell, Control system type: Safety Manager |
FC-GPCS-SAI16-PF |
Termination Board |
System board for Honeywell Safety Manager, For 16-channel AI card SAI-1620m, For 16 modules, Recommended module: HiC2025 (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: SiC plug, 20-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Honeywell, Control system type: Safety Manager |
FC-GPCS-SAO08-PF |
Termination Board |
System board for Honeywell Safety Manager, For 4 pieces 2-channel card SAO-0220m, For 8 modules, Recommended module: HiC2031 (AO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: SiC plug, 20-pin, Number of modules: 8, Signal type: Analog output, Manufacturer: Honeywell, Control system type: Safety Manager |
FC-GPCS-SDI16-PF |
Termination Board |
System board for Honeywell Safety Manager, For 16-channel DI cards SDIL-1608 and SDI-1624, For 16 modules, Recommended modules: HiC2821 (SIL 2), HiC2851 (SIL 3), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: SiC plug, 20-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Honeywell, Control system type: Safety Manager |
FC-GPCS-SDO08-PF |
Termination Board |
System board for Honeywell Safety Manager, For 8-channel card SDO-0824, For 8 modules, Recommended module: HiC2871 (DO), Hazardous area: pluggable screw terminals, blue, Non-hazardous area: SiC plug, 20-pin, Number of modules: 8, Signal type: Digital Output, Manufacturer: Honeywell, Control system type: Safety Manager |
FC-GPDD-SAI16-PF |
Termination Board |
System board for Honeywell Safety Manager, For 16-channel AI card SAI-1620m, For 8 modules, Recommended module: HiD2030 (AI), HiD2082 (TI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: SiC plug, 20-pin, Number of modules: 8, Signal type: Analog input, Manufacturer: Honeywell, Control system type: Safety Manager |
HiATB01-HART-4X8 |
HART Communication Board |
4 x 8-channel, 24 V DC supply, Suitable for HART communication, Dual RS 485 connections, Used with HiD/HiC Termination Boards, LED indicator for supply status, Splitting: 4 x 8 |
HiCTB08-FBM-RSC-SP-IO08-Y1 |
Termination Board |
System board for Schneider, Foxboro FBM series, For 8 modules, For 8-channel cards FBM201/214(b)/216(b) (AI), FBM215/218/237 (AO), FBM204/205 (AO/AI), FBM244 (AI/AO), FBM247/248 (UIO), 24 V DC supply, Recommended modules: HiC2025(A) (AI), HiC2031 (AO), HiC2081 (TI), HiC2831R5 (DI), HiC2883 (DO), HiC2441 (UIO), Hazardous area: spring terminals, blue, Non-hazardous area: Sub-D connector (male), 25-pin, Number of modules: 8, Signal type: Universal, Manufacturer: Foxboro, Control system type: FBM |
HiCTB08-SPT-44C-SP-RS-Y1 |
Termination Board |
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: spring terminals, blue, Non-hazardous area: spring terminals, black, Number of modules: 8, Number of channels per module: 1 , 2, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiCTB08-TRI-AOISS-EL-PL |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 8-channel AO card 3805E, For 8 modules, Recommended module: HiC2031 (AO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 8, Signal type: Analog output, Manufacturer: Triconex, Control system type: Tricon |
HiCTB08-YC3-RRB-KS-CC-AM08 |
Termination Board |
System board for Yokogawa CENTUM VP, For 8-channel AI card AAI135, For 8-channel AI/AO card AAI835, For 8 modules, Recommended modules: HiC2025(A) (AI), HiC2031 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 8, Signal type: Analog input/analog output, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiCTB08-YRS-RRB-AK-CC-DI16 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 16-channel DI card SDV144, For 8 modules, Recommended module: HiC2832R1 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 8, Signal type: Digital Input, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiCTB08-YRS-RRB-AK-CC-DO08 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 8-channel DO card SDV531, For 8 modules, Recommended module: HiC2871 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 8, Signal type: Digital Output, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiCTB08-YRS-RRB-AK-CC-DO08-Y1 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 8-channel DO card SDV531, For 8 modules, Recommended modules: HiC2883 (DO), HiC5861 (DO), HiC5863 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 8, Signal type: Digital Output, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiCTB08-YRS-RRB-KS-CC-AO08 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 8-channel AO card SAI533, For 8 modules, Recommended module: HiC2031 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 8, Signal type: Analog output, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiCTB16-FBM-RSC-SP-DI16 |
Termination Board |
System board for Schneider, Foxboro FBM series, For 16 modules, For 16-channel DI card FBM207b, 24 V DC supply, Recommended modules: HiC2821 (DI), HiC2841 (DI), Hazardous area: spring terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Foxboro, Control system type: FBM |
HiCTB16-SDC-44C-SC-RA |
Termination Board |
For 16 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Number of channels per module: 1 , 2, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiCTB16-TRI-AIISS-EL-PL |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 32-channel (16+16) AI cards 3700A, and 3721, For 16 modules, Recommended modules: HiC2025(A) (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon |
HiCTB16-TRI-DIISD-EL-PL |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 64-channel (32+32) DI card 3564, For 16 modules, Recommended module: HiC2822 (DI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon |
HiCTB16-TRI-DIISS-EL-PL |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 32-channel (16+16) DI card 3503E, For 16 modules, Recommended module: HiC2821 (DI), 24 V DC supply, Line fault detection (LFD), Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon |
HiCTB16-TRI-DIISS-EL-PL-Y1 |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, For 32-channel (16+16) DI cards 3503E and 3505E, For 16 modules, Recommended module: HiC2851 (DI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon |
HiCTB16-TRI-DOISS-EL-PL-Y1 |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 16-channel DO cards 3604E and 3624, For 16 modules, Recommended modules: HiC2873 (DO), HiC2877 (DO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Triconex, Control system type: Tricon |
HiCTB16-TRX-RSC-SP-AI16 |
Termination Board |
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel (16+16) AI cards 3722X and 3723X, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2081 (TI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon CX |
HiCTB16-TRX-RSC-SP-AI16-NEX |
Termination Board |
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel (16+16) AI cards 3722X and 3723X, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2081 (TI), 24 V DC supply, Field side: spring terminals, black, Control side: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon CX |
HiCTB16-TRX-RSC-SP-DI16 |
Termination Board |
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel (16+16) DI card 3506X, For 16 modules, 24 V DC supply, Recommended modules: HiC2821 (DI), HiC2841 (DI), Hazardous area: spring terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon CX |
HiCTB16-TRX-RSC-SP-DI16-NEX |
Termination Board |
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel (16+16) DI card 3506X, For 16 modules, 24 V DC supply, Recommended modules: HiC2821 (DI), HiC2841 (DI), Field side: spring terminals, black, Control side: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon CX |
HiCTB16-TRX-RSC-SP-DO16-NEX |
Termination Board |
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel (16+16) DO card 3626X, For 16 modules, Recommended modules: HiC2871A (DO), HiC2873 (DO), HiC2883 (DO), HiC5861 (DO), HiC5863 (DO), 24 V DC supply, Field side: spring terminals, black, Control side: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Triconex, Control system type: Tricon CX |
HiCTB16-YC3-RRB-KS-CC-AI16 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AI cards AAI143, AAB141-H, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2081 (TI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiCTB16-YC3-RRB-KS-CC-AI16-Y1 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AI card AAI141, For 16 modules, Recommended modules: HiC2025(A) (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiCTB16-YC3-RRB-KS-CC-AI16-Y2 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AI card AAV141, For 16 modules, Recommended module: HiC2025(A) (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiCTB16-YC3-RRB-KS-CC-AM16 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AI/AO card AAI841, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2031 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input/analog output, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiCTB16-YC3-RRB-KS-CC-AM16-Y1 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AI/AO card AAB841, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2031 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input/analog output, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiCTB16-YC3-RRB-KS-CC-AM16-Y2 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AI/AO card AAB842-H, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2031 (AO), HiC2081(TI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input/analog output, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiCTB16-YC3-RRB-KS-CC-AO16 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AO card AAI543, For 16 modules, Recommended module: HiC2031 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog output, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiCTB16-YRS-RRB-AK-CC-DI16 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 16-channel DI card SDV144, For 16 modules, Recommended modules: HiC2831R1 (DI), HiC2853R1 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiCTB16-YRS-RRB-AK-CC-DO16 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 16-channel DO card SDV541, For 16 modules, Recommended modules: HiC2871 (DO), HiC2873 (DO), HiC2877 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiCTB16-YRS-RRB-AK-CC-DO16-Y1 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 16-channel DO card SDV541, For 16 modules, Recommended modules: HiC2883 (DO), HiC5861 (DO), HiC5863 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiCTB16-YRS-RRB-KS-CC-AI16-Y1 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 16-channel AI card SAV144, For 16 modules, Recommended modules: HiC2025(A) (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiCTB32-SDC-24C-SC-RA |
Termination Board |
For 32 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 32, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiCTB32-TRI-AIISS-EL-PL |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, For 64-channel (32+32) AI cards 3704E and 3720, For 32 modules, Recommended modules: HiC2025(A) (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 32, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon |
HiCTB32-TRI-DIISS-EL-PL |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 64-channel (32+32) DI card 3564, For 32 modules, Recommended module: HiC2821 (DI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 32, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon |
HiCTB32-TRI-DOISS-EL-PL-Y1 |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 32-channel (16+16) DO cards 3625 and 3664, For 32 modules, Recommended modules: HiC2873 (DO), HiC2877 (DO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 32, Signal type: Digital Output, Manufacturer: Triconex, Control system type: Tricon |
HiCTB32-YC3-RRB-AK-CC-DX32 |
Termination Board |
System board for Yokogawa CENTUM VP, For 32-channel DI card ADV151, For 32 modules, Recommended module: HiC2821 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 32, Signal type: Digital Input, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiCTB32-YC3-RRB-AK-CC-DX32-Y1 |
Termination Board |
System board for Yokogawa CENTUM VP, For 32-channel DO card ADV551, For 32 modules, Recommended module: HiC2871 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 32, Signal type: Digital Output, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiDTB04-DVM-IDC1-SC-R1-DI16 |
Termination Board |
System board for Emerson DeltaV, For one 32-channel DI card via 40-pin Mass Termination Block, For 4 modules/16 channels, Recommended module: HiD2844 (DI), Volt-free fault indication output, 24 V DC supply, reverse polaritiy protected, optional daisychainable, Hazardous area: screw terminals, blue, Non-hazardous area: IDC connector, 20-pin, Number of modules: 4, Signal type: Digital Input, Manufacturer: Emerson, Control system type: DeltaV, M-Series |
HiDTB04-DVM-IDC1-SC-R2-DI16 |
Termination Board |
System board for Emerson DeltaV, For one 32-channel DI card via 40-pin Mass Termination Block, For 4 modules/16 channels, Recommended module: HiD2844 (DI), Volt-free fault indication output, 24 V DC supply, reverse polaritiy protected, optional daisychainable, Hazardous area: screw terminals, blue, Non-hazardous area: IDC connector, 20-pin, Number of modules: 4, Signal type: Digital Input, Manufacturer: Emerson, Control system type: DeltaV, M-Series |
HiDTB04-DVM-IDC3-SC-R2-DO08 |
Termination Board |
System board for Emerson DeltaV, For one 8-channel DO card via 16-pin Mass Termination Block, For one 32-channel DO card via 40-pin Mass Termination Block, For 4 modules/8 channels, Recommended module: HiD2872 (DO), Volt-free fault indication output, 24 V DC supply, reverse polaritiy protected, optional daisychainable, Hazardous area: screw terminals, blue, Non-hazardous area: IDC connector, 16 pin and 20-pin, Number of modules: 4, Signal type: Digital Output, Manufacturer: Emerson |
HiDTB04-DVM-IDC4-SC-NO-AM16 |
Termination Board |
System board for Emerson DeltaV, For two 8-channel AI/AO cards via 16-pin Mass Termination Block, For one 16-channel AI/AO card via 48-pin Mass Termination Block, For 4 modules/16 channels, Recommended module: HiD2024 (AI/AO), Line fault transparency (LFT), HART compatible, 24 V DC supply, reverse polaritiy protected, optional daisychainable, Hazardous area: screw terminals, blue, Non-hazardous area: IDC connector, 16 pin and 24-pin, Number of modules: 4, Signal type: Analog input/analog output |
HiDTB08-SCT-44C-SC-RA |
Termination Board |
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO, Hazardous area: screw terminals, blue, Non-hazardous area: screw terminals, black, Number of modules: 8, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiDTB08-SCT-49C-SC-RA |
Termination Board |
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO, Hazardous area: screw terminals, blue, Non-hazardous area: screw terminals, black, Number of modules: 8, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiDTB08-SDC-44C-SC-RA |
Termination Board |
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 8, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiDTB08-SDC-49C-SC-RA |
Termination Board |
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 8, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiDTB08-SDC-89C-SC-RA |
Termination Board |
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 8, Number of channels per module: 2 , 4, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiDTB08-TRI-AIISD-EL-PL |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 32-channel (16+16) AI cards 3700A, and 3721, For 8 modules, Recommended module: HiD2030 (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 8, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon |
HiDTB08-TRI-AIISD-EL-SC |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 32-channel (16+16) AI cards 3700A, and 3721, For 8 modules, Recommended modules: HiD2030 (AI), HiD2082 (TI), 24 V DC supply, Hazardous area: screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 8, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon |
HiDTB08-TRI-DIISQ-EL-SC |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 64-channel (32+32) DI card 3564, For 8 modules, Recommended modules: HiD2824 (DI), HiD2844 (DI), 24 V DC supply, Hazardous area: screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 8, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon |
HiDTB08-TRI-DOISD-EL-PL-Y1 |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 16-channel DO cards 3604E and 3624, For 8 modules, Recommended modules: HiD2872 (DO), HiD2876 (DO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 8, Signal type: Digital Output, Manufacturer: Triconex, Control system type: Tricon |
HiDTB08-YC3-RRB-AK-CC-DX32 |
Termination Board |
System board for Yokogawa CENTUM VP, For 32-channel DI card ADV151, For 8 modules, Recommended modules: HiD2824 (DI), HiD2844 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 8, Signal type: Digital Input, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiDTB08-YC3-RRB-KS-CC-AI16 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AI cards AAI141, AAI143, For 8 modules, Recommended modules: HiD2030 (AI), HiD2082 (TI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 8, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiDTB08-YC3-RRB-KS-CC-AM16-Y1 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AI/AO card AAI841, For 8 modules, Recommended modules: HiD2030 (AI), HiD2038 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 8, Signal type: Analog input/analog output, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiDTB08-YC3-RRB-KS-CC-AO16 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AO card AAI543, For 8 modules, Recommended module: HiD2038 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 8, Signal type: Analog output, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiDTB08-YRS-RRB-AK-CC-DO16 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 16-channel DO card SDV541, For 8 modules, Recommended modules: HiD2872 (DO), HiD2876 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 8, Signal type: Digital Output, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiDTB08-YRS-RRB-KS-CC-AI16 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 16-channel AI card SAI143, For 8 modules, Recommended module: HiD2030 (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 8, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiDTB08-YRS-RRB-KS-CC-AI16-Y2 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 16-channel AI card SAI143, For 8 modules, Recommended module: HiD2030 (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 8, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiDTB16-SCT-44C-SC-RA |
Termination Board |
For 16 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO, Hazardous area: screw terminals, blue, Non-hazardous area: screw terminals, black, Number of modules: 16, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiDTB16-SDC-44C-SC-RA |
Termination Board |
For 16 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Universal, Manufacturer: Universal, Control system type: Universal |
HiDTB16-TRI-AIISD-EL-PL |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 32-channel (16+16) AI cards 3700A, and 3721, For 16 modules, Recommended module: HiD2030 (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon |
HiDTB16-TRI-DIISQ-EL-SC |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 64-channel (32+32) DI card 3564, For 16 modules, Recommended modules: HiD2824 (DI), HiD2844 (DI), 24 V DC supply, Hazardous area: screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon |
HiDTB16-TRI-DOISD-EL-PL-Y2 |
Termination Board |
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 32-channel (16+16) DO cards 3625 and 3664, For 16 modules, Recommended modules: HiD2872 (DO), HiD2876 (DO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Triconex, Control system type: Tricon |
HiDTB16-YC3-RRB-AK-CC-DX32 |
Termination Board |
System board for Yokogawa CENTUM VP, For 32-channel DO card ADV551, For 16 modules, Recommended modules: HiD2872 (DO), HiD2876 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiS1132/CON8-H-LTX-02 |
HART Termination Board |
APACS/QUADLOG replacement FTA, Bailey Infi 90 replacement FTA, Product connector; PCS wiring, Easy switch selectable configurations for AO and AI, Number of channels: 32 unbalanced signal loops |
HiSHPMM/64/CONA-01 |
HART Termination Board |
64-channel, 24 V DC supply, Connection of two Multiplexers to HART enabled Honeywell TDC 3000 FTA's , Redundant power supply connections, Dual RS 485 connections, HART loop connection via four 20-pin flat ribbon connectors, Compact design, Number of channels: 64 unbalanced signal loops |
HiSHPSM/32/TB-02 |
HART Termination Board |
32-channel, 24 V DC supply, Interface for serial or parallel wiring options, 37-pin Sub-D connectors, Slot for HART Multiplexer, Number of channels: 32 unbalanced signal loops |
HiSHPSM/32/TB-02/HF32 |
HART Termination Board |
32-channel, 24 V DC supply, For analog output cards, HART output filters, Interface for serial or parallel wiring options, 37-pin Sub-D connectors, Slot for HART Multiplexer, Number of channels: 32 unbalanced signal loops |
HiSHPTB/32/FOX2001C-02 |
HART Termination Board |
IA 200 replacement FTA, Designed for FBMs 201, 204, 215 and 237, 25-pin Sub-D connectors, PCS wiring, Redundant power supply connections, Easy to add line impedance, Number of channels: 32 unbalanced signal loops |
HiSHPTB/32/HONB-AI-01 |
HART Termination Board |
TDC 3000 replacement FTA, Short-circuit protected, Process control system wirings, Redundant power supply connections, Field terminal blocks that are Honeywell FTA compatible, Honeywell "B" size footprint, Number of channels: 32 unbalanced signal loops |
HiSHPTB/32/HONB-AI-R-01 |
HART Termination Board |
TDC 3000 replacement FTA, Short-circuit protected, Redundant PCS wirings, Redundant power supply connections, Field terminal blocks that are Honeywell FTA compatible, Honeywell "B" size footprint, Number of channels: 32 unbalanced signal loops |
HiSHPTB/32/HONB-AO-R-01 |
HART Termination Board |
TDC 3000 replacement FTA, Short-circuit protected, HART analog output filters, Redundant PCS wirings, Redundant power supply connections, Field terminal blocks that are Honeywell FTA compatible, Honeywell "B" size footprint, Number of channels: 32 unbalanced signal loops |
HiSHPTB/32/TR-AI-01 |
HART Termination Board |
Triconex 3700A and 3721 replacement FTA, 2- or 3-wire or self powered transmitters, Outputs: 2 x 16 channels, 0 V ... 10 V differential, DC coupled (makes 32 channels), Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loops |
HiSHPTB/32/TR-AI-03 |
HART Termination Board |
Triconex 3704E and 3720 replacement FTA, 2- or 3-wire or self powered transmitters, Outputs: 1 x 32 channels, 0 V ... 5 V differential, DC coupled, Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loops |
HiSHPTB/32/TR-AO-01 |
HART Termination Board |
Triconex 3805E replacement FTA, 32 channels of I/O, Outputs: 4 x 8 channels, 4 mA ... 20 mA current loop, DC coupled, Short-circuit protected, HART analog output filters, Number of channels: 32 unbalanced signal loops |
SC-GPCD-DI32-PF |
Termination Board |
System board for Honeywell Experion PKS, Series C, For 32-channel card CC-TDIL01/11, For 16 modules, Recommended module: HiC2822 (DI), Recommended system cable: CAB-HON-**-S37C32-MX-01000, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Honeywell, Control system type: Experion PKS, Series C |
SC-GPDD-AIO16-PF |
Termination Board |
System board for Honeywell Experion PKS, Series C, For 16-channel cards CC-TAIX01/11 (AI) and CC-TAOX01/11 (AO), For 8 modules, Recommended modules: HiD2030SK (AI), HiD2082 (TI), HiD2038 (AO), Recommended system cable: CAB-HON-**-S37C32-MX-01000, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 8, Signal type: Analog input/analog output, Manufacturer: Honeywell, Control system type: Experion PKS, Series C |
SC-GPDD-DO32-PF |
Termination Board |
System board for Honeywell Experion PKS, Series C, For 32-channel card CC-TDOB01/11, For 16 modules, Recommended module: HiD2872 (DO), Recommended system cable: CAB-HON-**-S37C32-MX-01000, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Honeywell, Control system type: Experion PKS, Series C |
HiCTB16-HIM-RAC-SP-AO1601 |
Termination Board |
System board for HIMA, HIMax, For 16-channel card X-AO 1601 (AO, single mode), 16-channel card X-AO 1601 (AO, redundant mode on request), For 16 modules, Recommended module: HiC2031 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Number of modules: 16, Signal type: Analog output, Manufacturer: HIMA, Control system type: HIMax |
HiCTB16-HIM-RAC-SP-DI3202 |
Termination Board |
System board for HIMA, HIMax, For 32-channel card X-DI 32 02 (DI), For 16 modules, Recommended module: HiC2832 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: HIMA, Control system type: HIMax |
HiCTB16-HIM-RAC-SP-DI320X |
Termination Board |
System board for HIMA, HIMax, For 32-channel cards X-DI 32 01 or X-DI 32 04 (DI), For 16 modules, Recommended modules: HiC2822 (DI), HiC2842 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: HIMA, Control system type: HIMax |
HiCTB32-HIM-RAC-SP-AI320X |
Termination Board |
System board for HIMA, HIMax, For 32-channel cards X-AI 32 01 or X-AI 32 02 (AI), For 32 modules, Recommended modules: HiC2025(A) (AI), HiC2081 (TI), HiC2441 (UIO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Number of modules: 32, Signal type: Analog input, Manufacturer: HIMA, Control system type: HIMax |
HiCTB32-HIM-RAC-SP-DI3202 |
Termination Board |
System board for HIMA, HIMax, For 32-channel card X-DI 32 02 (DI), For 32 modules, Recommended modules: HiC2831 (DI), HiC2853 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Number of modules: 32, Signal type: Digital Input, Manufacturer: HIMA, Control system type: HIMax |
HiCTB32-HIM-RAC-SP-DI320X |
Termination Board |
System board for HIMA, HIMax, For 32-channel cards X-DI 32 01 or X-DI 32 04 (DI), For 32 modules, Recommended modules: HiC2441 (UIO), HiC2821 (DI), HiC2841 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Number of modules: 32, Signal type: Digital Input, Manufacturer: HIMA, Control system type: HIMax |
HiCTB32-HIM-RAC-SP-DO3201 |
Termination Board |
System board for HIMA, HIMax, For 32-channel card X-DO 32 01 (DO), For 32 modules, Recommended modules: HiC2873 (DO), HiC2883 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Number of modules: 32, Signal type: Digital Output, Manufacturer: HIMA, Control system type: HIMax |
HiCTB32-HIM-RAS-SP-AI320X |
Termination Board |
System board for HIMA, HIMax, For 32-channel cards X-AI 32 01 or X-AI 32 02 (AI), For 32 modules, Recommended module: HiC2027 (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Non-hazardous area: spring terminals, black, Number of modules: 32, Signal type: Analog input, Manufacturer: HIMA, Control system type: HIMax |
HiCTB32-HIM-RAS-SP-DI3202 |
Termination Board |
System board for HIMA, HIMax, For 32-channel card X-DI 32 02 (DI), For 32 modules, Recommended modules: HiC2831 (DI), HiC2853 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Non-hazardous area: spring terminals, black, Number of modules: 32, Signal type: Digital Input, Manufacturer: HIMA, Control system type: HIMax |
HiCTB32-HIM-RAS-SP-DI320X |
Termination Board |
System board for HIMA, HIMax, For 32-channel cards X-DI 32 01 or X-DI 32 04 (DI), For 32 modules, Recommended modules: HiC2821 (DI), HiC2841 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Non-hazardous area: spring terminals, black, Number of modules: 32, Signal type: Digital Input, Manufacturer: HIMA, Control system type: HIMax |
HiDTB08-DVM-IDC4-SC-R1-SM32 |
Termination Board |
System board for Emerson DeltaV, For two 8-channel AI/AO/DO cards via 16-pin Mass Termination Block, For four 8-channel DI cards via 16-pin Mass Termination Block, For 8 modules/16 or 32 channels, Recommended modules: HiD2030SK (AI), HiD2038 (AO), HiD2824 (DI), HiD2844 (DI), HiD2872 (DO), Volt-free fault indication output, 24 V DC supply, Hazardous area: screw terminals, blue, Non-hazardous area: IDC connector, 16-pin, Number of modules: 8, Number of channels per module: 2 , 4, Signal type: Universal |
HiDTB16-HIM-RAC-SP-AI320X |
Termination Board |
System board for HIMA, HIMax, For 32-channel cards X-AI 32 01 or X-AI 32 02 (AI), For 16 modules, Recommended modules: HiD2030 (AI), HiD2082 (TI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: HIMA, Control system type: HIMax |
HiDTB16-HIM-RAC-SP-DO3201 |
Termination Board |
System board for HIMA, HIMax, For 32-channel card X-DO 32 01 (DO), For 16 modules, Recommended module: HiD2872 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: HIMA, Control system type: HIMax |
HiDTB08-YC3-RRB-KS-CC-AI16-Y1 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AI card AAV141, For 8 modules, Recommended module: HiD2030 (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 8, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiDTB08-YRS-RRB-KS-CC-AI16-Y1 |
Termination Board |
System board for Yokogawa ProSafe-RS, For 16-channel AI card SAV144, For 8 modules, Recommended module: HiD2030 (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 8, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: ProSafe-RS |
HiSHPTB/32/TR-AI-02 |
HART Termination Board |
Triconex 3701 replacement FTA, 2- or 3-wire or self powered transmitters, Outputs: 2 x 16 channels, 0 V ... 10 V differential, DC coupled (makes 32 channels), Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loops |
HiSHPTB/32/YOK-AI-R-02 |
HART Termination Board |
Yokogawa Centum 3000 CS AAI135 replacement FTA, 32 channels of I/O, 2- or 3-wire or self powered transmitters, Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loops |
HiSHPTB/32/YOK-AIO-R-02 |
HART Termination Board |
Yokogawa Centum 3000 CS AAI835 replacement FTA, 32 channels of I/O, 16 channels AI and 16 channels AO, 2- or 3-wire or self powered transmitters or valves, Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loops |
HiSHPTB/32/TR-DO-01 |
HART Termination Board |
Triconex 3604E replacement FTA, Outputs: 2 x 16 channels, 24 V DC, opto-isolated, non commoned, Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loops |
HiDTB08-YC3-RRB-KS-CC-AM16 |
Termination Board |
System board for Yokogawa CENTUM VP, For 16-channel AI/AO card AAB841, For 8 modules, Recommended modules: HiD2030 (AI), HiD2038 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 8, Signal type: Analog input/analog output, Manufacturer: Yokogawa, Control system type: CENTUM VP |
HiSHPTB/32/TR-AI-01-Y1 |
HART Termination Board |
Triconex 3700A and 3721 replacement FTA, 2- or 3-wire or self powered transmitters, Outputs: 2 x 16 channels, 0 V ... 10 V differential, DC coupled (makes 32 channels), Short-circuit protected, Plug-n-play wiring capabilities, Optimized for use in floating power configurations, Number of channels: 32 unbalanced signal loops |
HONGKONG XIEYUAN TECH CO.,LTD, established in 7th Nov.,2012, a comprehensive corporation with its independent rights of export and import.. We are committed to providing customers with convenient and efficient industrial supplies services. From the product, price, logistics, service process for customers to improve procurement efficiency, reduce procurement costs, and grow together with customers.
Xieyuan sales of major brands are: Yokogawa, Siemens, ABB, Schneider, Emerson, Rosemount, Honeywell, Pepper+Fuchs, MTL, Fluke, Fisher, Endress+Hauser, Phoenix Contact, Weidmüller, Triconex, KROHNE, Dräger, Allen-Bradley, Omron, Eaton, SMC, Eaton, RAE, Testo, MSA, FESTO, Vega, Yaskawa, Danfoss, GE, Fisher, Hirschmann, IFM, Turck, MOXA, Foxboro etc.
Our wide range of products include Field Instruments, Field Communicator, Gas Detectors, Process Analyzers, Pressure Transmitters, Temperature Transmitters, Flow Meters, Inverters, Multimeters, Safety Barriers, Positioners, Controllers, Valves, Circuit Breakers, Sensors, DCS, PLC etc.
We endeavor to provide our customer with high quality, 100% original brand new products at competitive prices. Our targeting market includes Oil and Gas Industry, Refinery, Chemical, Mineral, Power and Energy, Ocean Engneering, Electricity, Food, Environment Protection and many other fields.
We operate in more than 50 countries around the world. There are: Singapore, Indonesia, Malaysia, Philippines, Vietnam, Thailand, South Korea, Kazakhstan, Bangladesh, United Arab Emirates, Saudi Arabia, Iran, Iraq, Kuwait, Oman, Qatar,Germany, Italy, Austria, UK, Nigeria, Pakistan, Egypt, USA, Chile, Brazil, Mexico etc.
CHINA MAINLAND ADDRESS:
7-A16,CAISHEN COMMERCIAL PLAZA, HANKOU RAILWAY STATION, WUHAN, CHINA.
All products will send out within 72 hours, Please feel free to contact us! Thanks
Windy Wang
HONGKONG XIEYUAN TECH CO., LIMITED
Add: 7-A16,Caishen Commercial Plaza,Hankou Railway Station,Wuhan,China
Tel: +86-27-8588 3233 | Fax:+86-27-8530 9780 | Mobile/Whatsapp :+86 15972199006 | Skype: windy@hkxytech.com
Mail: windy@hkxytech.com