Pepperl+Fuchs FieldBarrier RD0-FB-Ex4 In Good Price With Ready Stock
Features of RD0-FB-Ex4
• 4 outputs Ex ia IIC
• FieldBarrier in Zone 1/Div. 2
• Instruments in Zone 0...1/Div. 1
• Short circuit current limitation per output
• For FOUNDATION Fieldbus H1 and PROFIBUS PA
• Power, Com, and Error LEDs
• Supports FISCO and Entity
• Integrated cable tie-downs
• Supports all grounding methods
General specifications of RD0-FB-Ex4
Design / Mounting Cabinet installation
Fieldbus interface
Main cable (Trunk)
Connection input (Trunk IN): terminals 3+, 4-, 5s
output (Trunk OUT): terminals 7-, 8+, 6s
Rated voltage 32 ... 16 V DC
Rated current 31 mA ... 26 mA (without load)
77 mA ... 115 mA (at 20 mA load per input)
120 mA ... 209 mA (at 40 mA load per input)
135 mA ... 241 mA (short-circuit on all outputs)
Voltage drop trunk IN to trunk OUT 100 mV max.
Number of couplers max. 4 per segment
Outputs
Number of devices per output 1
Connection output 1: terminals 10+, 11-, 12S shield;
output 2: terminals 13+, 14-, 15S shield;
output 3: terminals 16+, 17-, 18S shield;
output 4: terminals 19+, 20-, 21S shield
Rated voltage 10 ... 13 V
Rated current ≤ 43 mA
Short-circuit current 50 mA
Terminating impedance 100 Ω switchable
Indicators/operating means
LED voltage Fieldbus green: on, bus voltage existent
LED status output red flashing: short-circuit
Galvanic isolation
Main wire/outputs isolation is not affected by interference according to EN 50020, voltage peak value 375 V
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013
Standard conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC/EN 60529
Fieldbus standard IEC 61158-2
Climatic conditions DIN IEC 721
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Ambient conditions
Ambient temperature -50 ... 70 °C (-58 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type fixed terminals, plug-in terminals
Core cross-section up to 2.5 mm2
Housing see figure 1
Housing material Polycarbonate
R... DIN rail housing PA 6.6
Degree of protection IP20
Mass 1050 g
Mounting mounting on DIN rail in cabinet
Data for application in connection
with hazardous areas
EU-Type Examination Certificate PTB 02 ATEX 2086
Marking ¬ II 2 (1) G Ex eb mb [ia Ga] IIC T4 Gb ,
¬ II (1) D [Ex ia Da] IIIC
Main cable (Trunk)
Maximum safe voltage Um 253 V AC
Outputs
Power Po 975 mW
Voltage Uo 15.75 V
Current Io 248 mA
Directive conformity
Directive 2014/34/EU EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-18:2015 , EN 60079-31:2013
International approvals
FM approval CoC 3015728
Control drawing No. 116-0226
Approved for Class I, Division 2, Groups A, B, C, D / Class I, Zone 2, AEx nA [ia] IIC T4
R4D0-FB-IA*
FieldBarrier® for Cabinet Installation
FieldConnex® FieldBarrier®, 8 ... 12 outputs Ex ia IIC, FISCO and Entity, Advanced fault isolation and diagnostics at the spur, FieldBarrier in Zone 1/Div. 2, Instruments in Zone 0...1/Div. 1, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Dust protection, International, Europe, USA, Device coupler location: Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk
R8D0-MIO-Ex12.FF*
Multi-Input/Output Device for Cabinet Installation
For discrete inputs and outputs, Installation in Zone 1/Div. 1, intrinsically safe, Sensors in Zone 0/Div. 1, Connection to fieldbus acc. to FISCO or Entity, For FOUNDATION Fieldbus H1, IECEx approval, Dust protection, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunk
R8D0-MIO-Ex12.PA*
Multi-Input/Output Device for Cabinet Installation
For discrete inputs and outputs, Installation in Zone 1/Div. 1, intrinsically safe, Sensors in Zone 0/Div. 1, Connection to fieldbus acc. to FISCO or Entity, For PROFIBUS PA, IECEx approval, Dust protection, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunk
RD0-FB-Ex4.*
FieldBarrier®
4 outputs Ex ia IIC, FieldBarrier in Zone 1/Div. 2, Instruments in Zone 0...1/Div. 1, Short circuit current limitation per output, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Dust protection, International, Europe, USA, Canada, Device coupler location: Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 1 - high-power trunk
RD0-TI-Ex8.FF.*
Temperature Multi-Input Device for Cabinet Installation
For 8 temperature or analog sensors, Installation in Zone 1/Div. 1, intrinsically safe, Sensors in Zone 0/Div. 1, Connection to fieldbus acc. to FISCO or Entity, For FOUNDATION Fieldbus H1, IECEx approval, Dust protection, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunk
RD0-TI-Ex8.PA.*
Temperature Multi-Input Device for Cabinet Installation
For 8 temperature or analog sensors, Installation in Zone 1/Div. 1, intrinsically safe, Sensors in Zone 0/Div. 1, Connection to fieldbus acc. to FISCO or Entity, For PROFIBUS PA, IECEx approval, Dust protection, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunk
SCP-LBF-IA1.36.IE*
Pluggable, mounts between device coupler and spur cable, Intrinsically safe (Ex ia), FISCO, Entity, DART Fieldbus, or general-purpose, Optional diagnostics for wear, Grounding of shield via gas-discharge tube, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk
SPJB-**-AL*.***
Segment Protector Junction Box, Aluminum
Intrinsically safe (Ex ic)/non-incendive outputs, Anodized aluminum, IP67, Configurable cable entries for trunk and spurs, Packaged solution, For FOUNDATION Fieldbus H1 and PROFIBUS PA, USA, Canada, Device coupler location: Division 2 - high-power trunk, Instrument location / spur protection: Division 2 - all relevant types of protection, Function: Device coupler, Design / Mounting: Outside installation
SPJB-**-CS*.***
Segment Protector Junction Box, Carbon Steel
Intrinsically safe (Ex ic)/non-incendive outputs, Carbon steel, NEMA 4, Configurable cable entries for trunk and spurs, Packaged solution, For FOUNDATION Fieldbus H1 and PROFIBUS PA, USA, Canada, Device coupler location: Division 2 - high-power trunk, Instrument location / spur protection: Division 2 - all relevant types of protection, Function: Device coupler, Design / Mounting: Outside installation
SPJB-**-FB*.***
Segment Protector Junction Box, Polyester (GRP)
Intrinsically safe (Ex ic)/non-incendive outputs, Glass fiber reinforced polyester, NEMA 4x, Configurable cable entries for trunk and spurs, Packaged solution, For FOUNDATION Fieldbus H1 and PROFIBUS PA, USA, Canada, Device coupler location: Division 2 - high-power trunk, Instrument location / spur protection: Division 2 - all relevant types of protection, Function: Device coupler, Design / Mounting: Outside installation
SPJB-**-PCW.***
Segment Protector Junction Box, Polycarbonate
Intrinsically safe (Ex ic)/non-incendive outputs, Impact resistant polycarbonate, NEMA 4x, Configurable cable entries for trunk and spurs, Packaged solution, For FOUNDATION Fieldbus H1 and PROFIBUS PA, USA, Canada, Device coupler location: Division 2 - high-power trunk, Instrument location / spur protection: Division 2 - all relevant types of protection, Function: Device coupler, Design / Mounting: Outside installation
SPJB-**-SS*.***
Segment Protector Junction Box, Stainless Steel
Intrinsically safe (Ex ic)/non-incendive outputs, Stainless steel, brushed NEMA 4x, Configurable cable entries for trunk and spurs, Packaged solution, For FOUNDATION Fieldbus H1 and PROFIBUS PA, USA, Canada, Device coupler location: Division 2 - high-power trunk, Instrument location / spur protection: Division 2 - all relevant types of protection, Function: Device coupler, Design / Mounting: Outside installation
TCP-LBF-IA1.36.IE*
Fieldbus Surge Protector, Field Installation on Trunk
Pluggable, mounts between device coupler and trunk cable, Intrinsically safe (Ex ia), FISCO, Entity, DART Fieldbus, or general-purpose, Optional diagnostics for wear, Grounding of shield via gas-discharge tube, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk
TPH-LBF-IA1.36.DE*
Fieldbus Surge Protector, Trunk Installation on Power Hub
Pluggable, mounts between Power Hub and trunk cable, Intrinsically safe (Ex ia), FISCO, Entity, DART Fieldbus, or general-purpose, Optional diagnostics for wear, Grounding of shield direct, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunk
HONGKONG XIEYUAN TECH CO.,LTD, established in 7th Nov.,2012, a comprehensive corporation with its independent rights of export and import.. We are committed to providing customers with convenient and efficient industrial supplies services. From the product, price, logistics, service process for customers to improve procurement efficiency, reduce procurement costs, and grow together with customers.
Xieyuan sales of major brands are: Yokogawa, Siemens, ABB, Schneider, Emerson, Rosemount, Honeywell, Pepper+Fuchs, MTL, Fluke, Fisher, Endress+Hauser, Phoenix Contact, Weidmüller, Triconex, KROHNE, Dräger, Allen-Bradley, Omron, Eaton, SMC, Eaton, RAE, Testo, MSA, FESTO, Vega, Yaskawa, Danfoss, GE, Fisher, Hirschmann, IFM, Turck, MOXA, Foxboro etc.
Our wide range of products include Field Instruments, Field Communicator, Gas Detectors, Process Analyzers, Pressure Transmitters, Temperature Transmitters, Flow Meters, Inverters, Multimeters, Safety Barriers, Positioners, Controllers, Valves, Circuit Breakers, Sensors, DCS, PLC etc.
We endeavor to provide our customer with high quality, 100% original brand new products at competitive prices. Our targeting market includes Oil and Gas Industry, Refinery, Chemical, Mineral, Power and Energy, Ocean Engneering, Electricity, Food, Environment Protection and many other fields.
We operate in more than 50 countries around the world. There are: Singapore, Indonesia, Malaysia, Philippines, Vietnam, Thailand, South Korea, Kazakhstan, Bangladesh, United Arab Emirates, Saudi Arabia, Iran, Iraq, Kuwait, Oman, Qatar,Germany, Italy, Austria, UK, Nigeria, Pakistan, Egypt, USA, Chile, Brazil, Mexico etc.
CHINA MAINLAND ADDRESS:
7-A16,CAISHEN COMMERCIAL PLAZA, HANKOU RAILWAY STATION, WUHAN, CHINA.
All products will send out within 72 hours, Please feel free to contact us! Thanks
Windy Wang
HONGKONG XIEYUAN TECH CO., LIMITED
Add: 7-A16,Caishen Commercial Plaza,Hankou Railway Station,Wuhan,China
Tel: +86-27-8588 3233 | Fax:+86-27-8530 9780 | Mobile/Whatsapp :+86 15972199006 | Skype: windy@hkxytech.com
Mail: windy@hkxytech.com
Website: http://www.hkxytech.com/ | GMT/UTC +8